                                                                                                                     TECH TIPS
                                                                                                                              www.conspectusinc.com
                                                                                                                     Vol12.10.01 ©2012 Conspectus Inc.
                                                                                                                                         Page 1 of 2
                 Providing compete                                        Floor Slab Flatness & Levelness
                 construction specifications                                                By David Stutzman, AIA, CSI, CCS, SCIP, LEED AP
                 documentation, systems 
                 and performance                                Background                                  such as for narrow aisle and 
                 descriptions, and risk and                                                                 automated warehouses, special
                 quality advisory services.                     Traditionally allowable tolerances of       consideration must be given to 
                                                                concrete floor slabs were determined        concrete placement and tolerance 
                 Conspectus's Tech Tips received the            by checking the slab surface with a         measurements. These conditions are 
                 national Communications Award from             10 foot straightedge. Common                not addressed by ACI 117.
                 the Construction Specifications                tolerances were 1/8 inch or 1/4 inch 
                 Institute September 2011.                                                                  F-Number Method
                                                                in 10 feet.
                 ABSTRACT:                                      The fallacy of the straightedge 
                 Ensure concrete finishing                      method was the location of the              The ASTM standard, in place for two 
                 specifications include all the                 measurement. Depending on where             decades, establishes the method for 
                 information required for floor slab            the measurement was made, the slab          measuring F-Numbers. The method 
                 tolerances. Specifying single values           may pass or fail the specified              uses a statistical analysis of 
                 for flatness and levelness may result          tolerance. Until recently, no standard      measured points 12 inches apart 
                 in ambiguous requirements. F-
                 Number and straightedge methods                procedure existed for taking                taken along straight lines in a 
                 require two sets of values to ensure           straightedge measurements.                  prescribed pattern within each sample 
                 the expected results are clearly               In 1979 Allen Face introduced the           panel. Each sample panel must 
                 stated.                                        Face Floor Profile Numbering System         exceed 320 sf, must be at least 8 ft. 
                 FILING:                                        (F-Numbers) to remove the ambiguity         wide, and must not cross a 
                 UniFormat™                                     of measuring floor flatness and             construction joint.
                 A4010 Standard Slabs-on-Grade                  levelness. F-Numbers use                    The ACI standard sets recommended 
                 A4020 Structural Slabs-on-Grade                dimensionless symbols to designate          F-Number tolerances for various 
                 B1010 Floor Construction                       flatness and levelness. F-Numbers           concrete floor slab construction 
                 MasterFormat™                                  formalized in 1987 by ASTM E1155            qualities. To specify F-Numbers 
                 03 30 00 Cast-In-Place Concrete                and ASTM E1155M were adopted by             correctly, two values are required for 
                                                                the American Concrete Institute as          flatness and levelness: 
                 KEYWORDS:                                      the standard for specifying floor            Specified Overall (SOF  and SOF )
                 Flatness, Levelness, F-Numbers,                tolerances in 1990 in ACI 117.                                         F          L
                 Straightedge, Specified overall                                                             Minimum Local (MLF  and MLF )
                                                                   F  Floor Flatness - variation from                               F          L
                 values, Minimum local values, Allen                  F
                 Face                                               surface plane (bumpiness)               Floor Surface          SOF         SOF
                                                                                                            Classification             F           L
                                                                   F  Floor Levelness - variation from 
                 REFERENCES:                                          L                                     Conventional            20          15
                 ACI 117 - Standard Specifications for              horizontal plane (pitch)
                 Tolerances for Concrete Construction                                                       Moderately Flat         25          20
                 and Materials                                  Specifications referencing ACI 117          Flat                    35          25
                 ASTM E1155 - Standard Test Method              for tolerances may rely on 
                 for Determining FF Floor Flatness and          F-Numbers or manual straightedge            Very Flat               45          35
                 FL Floor Levelness Numbers                     methods to determine floor slab 
                 ASTM E1155M - Standard Test                                                                Super Flat              60          40
                 Method for Determining FF Floor                tolerances for random traffic pattern 
                 Flatness and FL Floor Levelness                floors which are typical for most uses.     F-Numbers must be measured within 
                 Numbers (Metric)                               However straightedge measurements           72 hours of placing the slab. This 
                                                                are not permitted for very flat and         ensures that the F-Numbers are 
                                                                super flat floors.                          measuring the concrete contractor's 
                                                                When defined traffic patterns exist         quality. 
                                                                                                                    TECH TIPS
                                                                                                                             www.conspectusinc.com
                                                                                                                   Vol12.10.01 ©2012 Conspectus Inc.
                                                                                                                                       Page 2 of 2
                If the measurements are delayed,                                 Maximum Gap            Very flat floors are usually restricted 
                shrinkage, curling, and other factors       Floor Surface                               to high-end industrial applications
                outside the concrete contractor's           Classification     90%          100%        where high speed fork trucks and 
                                                                           Compliance Compliance        other high-production equipment are 
                control can influence the results.          Conventional     1/2 inch     3/4 inch
                Levelness tolerances apply only to                                                      used.
                slabs-on-grade and suspended slabs          Moderately       3/8 inch     5/8 inch      Super flat floors are appropriate for 
                 that are shored when tested.               Flat                                        very limited applications with random 
                Levelness tolerances do not apply to        Flat             1/4 inch     3/8 inch      traffic such as television production 
                sloped or cambered floors.                                                              studios to minimize camera vibration.
                ACI 117 sets the Minimum Local              Very Flat          N/A           N/A
                values at 60% of the Specified Overall      Super Flat         N/A           N/A        Specification Tip
                values, unless specified otherwise.         The familiar 1/8 inch in 10 feet 
                The Minimum Local values are the            tolerance is not an option with ACI         Select the method: F-Number or 
                minimum tolerances for the floor to be      117. This may present difficulties for      manual straightedge. Reference ACI 
                usable. Defects exceeding the               specifying slab tolerances for applied      117 for tolerance compliance.
                Minimum Local values normally               floor finishes, such as wood strip          Allen Face provides an F-Number 
                require grinding, filling, or replacement   flooring. Some floor finish                 sample specification. Include the 
                to correct the defect.                      manufacturers require more stringent        minimum Specified Overall and the 
                For a slab to be acceptable, the            tolerances than can be tested using         Minimum Local values for both 
                cumulative Overall Values for the           the straightedge method. Consult the        flatness and levelness.
                entire slab must meet or exceed the         finish flooring manufacturer's              For the manual straightedge method, 
                Specified Overall values, and all           instructions for acceptable substrate       specify the maximum gap for 90% and 
                locations must meet or exceed the           surfaces.                                   100% compliance.
                Minimum Local values.
                Straightedge Method                         Floor Classifications
                                                            The floor classifications above are for 
                In the June 2010 edition of ACI 117,        random traffic patterns. More stringent 
                the straightedge method description         tolerances require additional 
                was greatly expanded. Now the               straightening operations, time, and 
                standard establishes a procedure for        cost to ensure compliance. Very flat 
                measuring flatness with a                   and super flat floors require 
                straightedge. Note that levelness           specialized equipment and specially 
                cannot be determined with a                 trained mechanics to achieve the            Add Your Comments
                straightedge. ACI 117 sets minimum          results.                                    We invite your comments. Visit our blog 
                sampling requirements to help ensure        Conventional floors are not suitable        and add your comments.
                a statistically representative set of       for applied finishes. These floors are 
                measurements. One sample must be            used for utility spaces and are usually     Like it? Share it!
                taken for every 100 sf of floor area.       left exposed.                               Tweet or Email your friends
                Samples must be taken parallel,             Moderately flat floors are suitable for 
                perpendicular, or at a 45 degree angle      carpeted finishes in commercial 
                to the longest construction joint of the    buildings and low speed vehicular           The information contained in this document 
                test area.                                  traffic in industrial buildings.            is offered for educational purposes, only, 
                The following chart shows the               Flat floors are suitable for thin set       and not as technical advice suitable for any 
                maximum gap between the floor               ceramic tile, vinyl tile and similar        particular project or specific condition. 
                surface and the bottom of the 10 foot       finishes and for conventional fork          Technical consulting is unique to the facts 
                straightedge. Note that                     truck traffic in warehouses. Flat floor     of a particular condition, and Conspectus 
                90% of the samples must not exceed          classification is the most stringent        recommends that a specialist be consulted 
                column 2 and 100% of the samples            tolerance that should be expected for       to determine solutions for each specific 
                must not exceed column 3 of the table       suspended slabs.                            condition.
                below.
The words contained in this file might help you see if this file matches what you are looking for:

...Tech tips www conspectusinc com vol conspectus inc page of providing compete floor slab flatness levelness construction specifications by david stutzman aia csi ccs scip leed ap documentation systems and performance background such as for narrow aisle descriptions risk automated warehouses special quality advisory services traditionally allowable tolerances consideration must be given to concrete slabs were determined placement tolerance s received the checking surface with a measurements these conditions are national communications award from foot straightedge common not addressed aci inch or institute september f number method in feet abstract fallacy ensure finishing was location astm standard place two include all measurement depending on where decades establishes information required made measuring numbers specifying single values may pass fail specified uses statistical analysis result until recently no measured points inches apart ambiguous requirements methods procedure existed...